Siemens SKP15.011U1 Gas Valve Actuator 120V Safety Shut-Off (ON/OFF)
Unsure if this is the right choice for your equipment or project? Our technical team can verify compatibility, check supporting parts, and provide recommendations before you purchase.
📋 This message will include the product details and SKU you are currently viewing so we can discuss the exact parts with you.
Delivery and Shipping
Technical Support On Hand
- Obsolete replacement part assistance
- Comprehensive documentation library
- Commissioning Support
- Priority parts replacement service
Description
Siemens SKP15.011U1 Gas Valve Actuator (120V)
The Siemens SKP15.011U1 is an electro-hydraulic actuator used on industrial and commercial combustion systems where reliable gas valve operation and rapid fail-safe closure are required.
SKP15 actuators are safety-critical components. If an actuator fails, the valve may not complete its stroke correctly, often leading to burner lockout or shutdown. This unit is supplied for direct like-for-like replacement where the SKP15.011U1 is specified.
Compatibility and Use
- Used with Siemens gas valve bodies including: VGG, VGF, VGD2, VGD4, VRD, VRF
- Typical applications: industrial burners, boilers, ovens, dryers, and process heating systems
- Fail-safe spring-return closure on power loss (< 0.8 s on power loss)
- Function: Safety shut-off (ON/OFF)
Note: Always match the full Siemens part number and electrical specification shown on the actuator rating plate.
Technical Data
SKP15: Together with a compatible Siemens valve body, the actuator works exclusively as a safety shut-off valve actuator (OPEN/CLOSED).
Mains voltage: 120V
Stages: 1-stage
Switch configuration: WITHOUT end switch
Degree of protection: IP54
Weight: 1.1 kg
Opening time for full stroke: 6 to 10 s (depends on valve size)
Opening speed: approx. 2 mm/s
Switch options: Proof of Closure (POC): Yes; Auxiliary switch: No
Functional Operation
When the actuator is energised, an internal pump transfers hydraulic fluid within the actuator to build pressure in the stroke chamber. This drives the piston to open the gas valve against the return spring.
When power is removed, the pump stops and the internal relief path allows the return spring to drive the piston back, closing the valve quickly to a safe position.
Typical Failure Symptoms
- Gas valve not opening during start-up
- Burner fails to prove or locks out
- Actuator does not complete stroke
- Switch feedback not detected by the control system (where fitted)
Replacement Guidance
This actuator should be replaced like-for-like. Voltage, switch configuration, and functional type must match the original unit. If you are unsure whether SKP15.011U1 is correct for your valve, our technical team can confirm compatibility before ordering.
You can send a photo of the existing actuator rating plate or valve assembly to ensure correct selection.
Documentation
Manufacturer technical documentation and installation instructions should be followed during installation and commissioning.