Siemens LAL3.25 - 110V
Siemens (Landis) Part Number:BPZ:LAL3.25-110v
Difference to LAL1... / LAL2... / LAL4...: - Extraneous light does not initiate lockout †™ during burner off times during the prepurge time - Extraneous light prevents burner startup
Technical Specifications:
- Siemens LAL3.25 110V controls oil atomising burners.
- Semi-automatic Startup
- Supply Voltage: 110V
- Pre-purge time with air damper open: 22.5s
- Pre-ignition time: 2.5s
- Post-ignition time: 15s
- Post purge time: 15s
- Ignition safety time: 5s
- Permissible after-burn time: 15s